Screening method for rapid determination of polychlorinated biphenyls in transformer oil by liquid-liquid extraction and gas chromatography-mass spectrometry
Author | dc.contributor.author | Toledo, Carla | |
Author | dc.contributor.author | Valle, Luis | es_CL |
Author | dc.contributor.author | Narváez, Jessica | es_CL |
Author | dc.contributor.author | Richter Duk, Pablo | es_CL |
Admission date | dc.date.accessioned | 2009-08-04T10:12:00Z | |
Available date | dc.date.available | 2009-08-04T10:12:00Z | |
Publication date | dc.date.issued | 2007 | |
Cita de ítem | dc.identifier.citation | JOURNAL OF THE BRAZILIAN CHEMICAL SOCIETY 18(5):937-942 | en |
Identifier | dc.identifier.issn | 0103-5053 | |
Identifier | dc.identifier.uri | https://repositorio.uchile.cl/handle/2250/120751 | |
Abstract | dc.description.abstract | A rapid and simple method was developed for screening polychlorinated biphenyls in transformer oil. The method is based on liquid-liquid extraction in methanol and subsequent direct gas chromatography-mass spectrometric determination. The extent of methanol polarity allows to extract the PCBs, co-extracting a minimum amount of the apolar oil components, thus avoiding the time-consuming steps involving in sample preparation. Since the regulation established internationally for wastes containing PCBs is 50 mg kg(-1), the method rapidly determines whether the transformer oil is PCBs-contaminated or not. In order to reach the best conditions for extraction a multivariate optimization was carried out considering two significant variables: volume of methanol and extraction time. Under optimum conditions, recoveries of Aroclor 1256 and Aroclor 1260 were between 80 and 100%, and precision, expressed as relative standard deviation, was from 2 to 4%. The method was applied to real samples polluted with PCBs. | en |
Lenguage | dc.language.iso | en | en |
Publisher | dc.publisher | SOC BRASILEIRA QUIMICA | en |
Keywords | dc.subject | PCBS | en |
Título | dc.title | Screening method for rapid determination of polychlorinated biphenyls in transformer oil by liquid-liquid extraction and gas chromatography-mass spectrometry | en |
Document type | dc.type | Artículo de revista |
Files in this item
This item appears in the following Collection(s)
-
Artículos de revistas
Artículos de revistas